vertical and one 90° or 45° horizontal elbow). Tree of Life poêle à gaz
Horizontal Termination with Two Elbows
(
one 90° vertical and one 90° or 45° horizontal elbow
)
L’embout doit obligatoirement se trouver dans la zone hachurée du tableau. Utiliser les positions indiquées pour les restricteurs et le diffuseur.
19' max (5.8m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
19' max (5.8m)
Restrictor
Position # 5
Restrictor
Position # 1
NOTE:
Restrictor positions are based upon lab tests. The ideal restrictor position may vary slightly, especially when the termination is near a demarkation line.
NOTE:
Horizontal sections require a 1/4" (0.250mm) rise every 12" (305mm) of travel.
NATURAL GAS: Min. 2' (0.61m) Section Required
PROPANE (LP): Min. 3' (0.915m) Section Required
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
Horizontal Elbow
Horizontal elbows are elbows placed between two horizontal sections of pipe. One 45° or 90° horizontal elbow is allowed for this configuration.
© Travis Industries 4100326 100-01250_000